| TROUBLESHOOTING
PROBLEMS WITH A SD 75, 100, 150 OR 300 CONSTANT PRESSURE PUMP CONTROLLER CP Pump Controllers are SD Controllers DIAGNOSTICS FOR FAULT CODES |
|||
| FLASHERS Error Code |
FAULT | POSSIBLE CAUSE | CORRECTIVE ACTION |
| 1 | MOTOR
UNDERLOAD |
Overpumped
well Broken Shaft or Coupling Blocked Screen, Worn Pump Air/Gas Locked Pump SubDrive not set properly for pump end. |
Frequency
near maximum with less than 65% of expected load, 42% if DIP #3 is on. System is drawing down to pump inlet Out of Water High Static. light loading pump - reset DIP #3 to "on" for less sensitivity if not out of water. Check pump rotation (SubDrive only) reconnect if necessary for proper rotation. Air / Gas locked pump - if possible, set deeper in the well to reduce. Verify DIP switches are set properly. |
| 2 | UNDERVOLTAGE | Low
Line Voltage Misconnected input leads |
Line
voltage low, less than approximately 150 VAC (normal operating range is 190 - 260 VAC) Check incoming power connections and correct or tighten if necessary Correct incoming voltage - check circuit breaker or fuses, contact power company |
| 3 | LOCKED PUMP | Motor
and/or pump misallignment Dragging motor and/or pump Abrasives in pump |
Amperage
above SFL at 10 Hz Remove and repair or replace as required |
| 4 | INCORRECTLY WIRED |
MonoDrive
only Wrong resistance values on main and start |
Wrong
resistance on DC test at start Check wiring, check motor size and DIP switch setting, adjust or repair as needed |
| 5 | OPEN CIRCUIT | Loose
connection Defective motor or drop cable Wrong motor |
Open
reading on DC test at start Check drop cable and motor resistance, tighten output connections, repair or replace as necessary, use "dry" motor to check drive functions, if drive will not run and exhibits underload fault replace drive |
| 6 | SHORT CIRCUIT | Shorted
motor Damaged cable Damaged pump or motor |
Amperage
exceeded 50 amps on DC teat at start or SF amps during running Incorrect output wiring, phase to phase short, phase to ground short in wiring or motor If fault is present after resetting and removing motor leads, replace drive |
| 7 | OVERHEATED DRIVE |
High
ambient temperature Direct sunlight Obstruction of airflow |
Drive
heat sink has exceeded max rated temperature, needs to drop below 85 degrees C to restart Fan blocked or inoperable, ambient above 125 degrees F, direct sunlight, air flow blocked Repair, relocate as necessary, NEMA 1 or 3R fan failure - replace drive |
|
Power down, disconnect
leads to the motor and power up the SubDrive. |
|||
| SUBDRIVE TROUBLESHOOTING | |||
| CONDITION | INDICATOR LIGHTS |
POSSIBLE CAUSE |
CORRECTIVE ACTION |
| NO WATER | NONE | No supply voltage present | If correct voltage is present, replace drive |
| SOLID GREEN | Pressure sensor circuit | Verify water
pressure is below system set point. Jumper wires together at pressure sensor, if pump starts, replace sensor. If pump doesn't start, check sensor connection at PCB, if loose, repair. If pump doesn't start, jumper sensor connection at PCB, if pump starts, replace wire. If pump doesn't start with sensor PCB connection jumped, replace drive. |
|
| SOLID
RED OR SOLID RED AND GREEN |
Power Surge, bad component | Power
system down to clear fault, verify voltage, if repetitive, replace drive. |
|
| FLASHING RED | Fault detected | Proceed to fault code description and remedy. | |
| FLASHING GREEN | Drive
and motor are operating Loose switch or cable connection Gulping water at pump inlet. |
Frequency
max, amps low, check for closed valve or stuck check valve. Frequency max, amps high, check for hole in pipe. Frequency max, amps erratic, check pump operation, dragging impellers. This is not a drive problem. Check all connections. Disconnect power and allow well to recover for a short time, then retry. |
|
| PRESSURE FLUCTUATIONS (POOR REGULATION) |
FLASHING GREEN | Pressure
sensor replacement and setting Pressure gauge replacement Pressure tank size and precharge Leak in system Air entrainment into pump intake (lack of submergence) |
Correct
pressure and placement as necessary. Tank may be too small for system flow. This is not a drive problem. Disconnect power and check pressure gauge for pressure drop. Set deeper in the well or tank; install a flow sleeve with airtight seal around drop pipe and cable. If fluctuation is only on branches before sensor, flip DIP switch #4 to "on" (07C and newer). |
| RUN
ON WON'T SHUT OFF |
FLASHING GREEN | Pressure
sensor placement and setting Tank precharge pressure Impeller damage Leaky system Sized improperly (pump can't build enough head) |
Check
frequency at low flows, pressure setting may be to close to pump max head. Verify precharge at 70% if tank size is larger than minimum, increase precharge (up to 85%). Verify that the system will build and hold pressure. |
| RUNS BUT TRIPS | FLASHING RED | Check fault code and see corrective action | Proceed to fault code description and remedy. |
| LOW PRESSURE | FLASHING GREEN | Pressure
sensor setting, pump rotation, pump sizing |
Adjust
pressure sensor, check pump rotation. Check frequency at max flow, check maximum pressure. |
| HIGH PRESSURE | FLASHING GREEN | Pressure
sensor setting Shorted sensor wire |
Adjust
pressure sensor. Remove sensor wire at PCB, if drive continues to run, replace drive. Verify condition of sensor wire and repair or replace if necessary. |
| AUDIBLE NOISE | FLASHING GREEN | Fan, hydraulic, plumbing | For
excessive fan noise, drive must be replaces on NEMA 1 and 3R, fan is replaceable on NEMA 4. If fan noise is normal, drive will need to be relocated to a more remote area. If hydraulic, try raising or lowering depth of pump. Pressure tank location should be at entrance of water line into house. |
| NO LIGHTS | NONE | Ribbon
cable detached from LED printed Circuit board |
Reattach cable - if cable is attached, replace drive. |
| RFI-EMI INTERFERENCE |
FLASHING GREEN | See interference troubleshooting procedure. | |